azienda

Customers benchmark for innovation

Slogan

...

CHG 08 - 100

Low temperatures water chillers

  • Main features
  • Technical specifications
  • Dimensions
  • Brochures

CHG 08 - 100
Cooling capacity from 0,80 kW to 10,10 kW

AVAILABLE OPTIONS

  • All models - 60 Hz version
  • Automatic by-pass and manometer
  • Non-ferrous 4 or 6 bar pump
  • Low ambient temperature kit
  • Water level alarm
The low temperature liquid water chillers were designed to meet the needs of the chemical and food industries, to process and preserve products at temperatures near or below 0°C and are finding new industrial uses every day.
The CHG series has been developed to function with outlet water temperatures below 0°C.
These series utilize refrigerant gas R404a suitable for low temperature of outlet water.
All refrigerators are equipped with pump and tank.
Model Code Cooling capacity Power consumption Power supply Tank Datasheet
kW Kcal/h Btu/h kW A V/ph/Hz l Download
CHGM 08 06G.0008.34.000.T.A000 0,8 690 2730 1 6,1 230/1/50 10 Download
CHGT 24 06G.0024.30.000.T.A000 2,37 2040 8100 1,82 4,4 400/3/50 30 Download
CHGT 30 06G.0030.30.000.T.A000 3,15 2710 10760 2,22 5,3 400/3/50 30 Download
CHGT 45 06G.0045.30.000.T.A000 4,3 3700 14690 2,75 6,1 400/3/50 30 Download
CHGT 75 06G.0075.30.000.G.A000 7,1 6110 24250 4,75 10,5 400/3/50 60 Download
CHGT 100 06G.0100.30.000.G.A000 10,1 8690 34500 6,31 12,8 400/3/50 60 Download

    STANDARD REFERENCE CONDITIONS

  • Ambient temperature: 25°C
  • Fluid outlet temperature: -10°C
  • Fluid type: H2O + Glycol

    OPERATING TEMPERATURES

  • Fluid temperature: -15°C / 0°C (min/max)
  • Ambient temperature: +2°C / +40°C (min/max)
  • Only CHGM08: +15°C / +40°C
Model Dimensions (mm) Weight Connections
A B C Kg BSP
CHGM 08 445 575 540 52 ½"
CHGT 24 580 650 920 99 ¾"
CHGT 30 580 650 920 110 ¾"
CHGT 45 580 650 920 123 ¾"
CHGT 75 760 760 1335 140 ¾"
CHGT 100 760 760 1380 170 ¾"
CHGM 08
CHGT 24 - CHGT 45
CHGT 75 - CHGT 100